Description
FailSafe Super is available with a corrosion resistant fluoropolymer outer jacket (FSS-CF).
The installation of FailSafe Super is quick and simple and requires no special skills or tools. Termination, splicing and power connection components are all provided in convenient kits.
Example of Applications
- Freeze protection of pipework & vessels
- Process temperature maintenance
Benefits
- Can be cut to length
- Output self-regulates in response to pipe temperature
- High outputs to 75W/m at 10ºC
- Inherently Temperature Safe
| Maximum Continuous Exposure
Temperature (Power ON) |
225°C (437°F) |
| Maximum Permissable Exposure
Temperature (Power OFF) |
225°C (437°F) |
| Minimum Operating Temperature | -40ºC (-40ºF) |
| Temperature Classification | 15FSS – 60FSS T3 (200°C/392°F)
75FSS T2 (300°C/572°F) |
| Power Supply | 12 – 277 VAC |
| Cable Dimensions | FSS-CF 11.45 x 5.25mm
+/- 0.5mm |
| Minimum Installation Temperature | -40°C (-40°F) |
| Minimum Bending Radius | FSS- CF 35mm |
| Weight kg/100m | FSS-CF – 13.4 kg |
| Maximum Resistance of Protective Braiding | 18.2 Ohm/km |
| Cable Gland Thread Size | M20 |
| Maximum Circuit Length (m) for various circuit breaker sizes | ||||||
|---|---|---|---|---|---|---|
| Product Reference |
Start-Up Termperature (°C) |
230v
10A |
16A | 20A | 32A | 50A |
| 15FSS | 10 | 76 | 122 | 154 | 172 | 172 |
| 0 | 70 | 112 | 140 | 172 | 172 | |
| -20 | 62 | 98 | 122 | 172 | 172 | |
| -40 | 52 | 82 | 102 | 164 | 172 | |
| 30FSS | 10 | 52 | 82 | 102 | 122 | 122 |
| 0 | 46 | 74 | 92 | 122 | 122 | |
| -20 | 40 | 66 | 82 | 122 | 122 | |
| -40 | 34 | 54 | 68 | 110 | 122 | |
| 45FSS | 10 | 38 | 62 | 76 | 100 | 100 |
| 0 | 34 | 56 | 70 | 100 | 100 | |
| -20 | 30 | 50 | 62 | 98 | 100 | |
| -40 | 22 | 34 | 44 | 70 | 100 | |
| 60FSS | 10 | 30 | 50 | 62 | 86 | 86 |
| 0 | 28 | 44 | 56 | 86 | 86 | |
| -20 | 20 | 32 | 40 | 62 | 86 | |
| -40 | 12 | 18 | 24 | 38 | 60 | |
| 75FSS
|
10 | 24 | 40 | 50 | 76 | 76 |
| 0 | 18 | 30 | 38 | 60 | 76 | |
| -20 | 14 | 22 | 26 | 42 | 66 | |
| -40 | 8 | 12 | 16 | 26 | 40 | |
| For use with Type C circuit breakers to IEC 60898 | ||||||





Reviews