£34.80

FailSafe Ultimo is an industrial grade self-regulating heating cable that can be used for freeze protection or temperature maintenance of pipework and vessels. It can be cut-to-length on site to match exact piping lengths without any complicated design considerations.

FailSafe Ultimo is approved for use in non-hazardous, and hazardous areas to worldwide standards. Its self-regulating characteristics improve safety and reliability.

FailSafe Ultimo will not overheat or burnout, even when overlapped upon itself. Its power output self-regulates in response to the pipe temperature.

 

Description

FailSafe Ultimo is available with a corrosion resistant fluoropolymer outer jacket (FSU-NF).

The installation of FailSafe Ultimo is quick and simple and requires no special skills or tools. Termination, splicing and power connection components are all provided in convenient kits.

Example of Applications

  • Freeze protection of pipework & vessels
  • Process temperature maintenance

Benefits

  • Can be cut to length
  • Output self-regulates in response to pipe temperature
  • High outputs to 75W/m at 10ºC
  • Inherently Temperature Safe

Download Datasheet: FailSafe Ultimo (FSU/FSUW)

Maximum Continuous Exposure

Temperature (Power ON)

250°C (482°F)
Maximum Permissable Exposure

Temperature (Power OFF)

250°C (482°F)
Minimum Operating Temperature -40ºC (-40ºF)
Temperature Classification 15FSU – 60FSU T3 (200°C/392°F)

75FSU T2 (300°C/572°F)

Power Supply 12 – 277 VAC
Cable Dimensions FSU-NF 12.5 x 5.8mm +/- 0.5mm
Minimum Installation Temperature -40°C (-40°F)
Minimum Bending Radius FSU- NF – 35mm
Weight kg/100m FSU-NF – 14.6 kg
Maximum Resistance of Protective Braiding 18.2 Ohm/km
Cable Gland Thread Size FSU-NF – M20
 
Maximum Circuit Length (m) for various circuit breaker sizes
Product
Reference
Start-Up
Termperature (°C)
230v

10A

16A 20A 32A 50A
15FSU 10 76 122 154 172 172
0 70 112 140 172 172
-20 62 98 122 172 172
-40 52 82 102 164 172
30FSU 10 52 82 102 122 122
0 46 74 92 122 122
-20 40 66 82 122 122
-40 34 54 68 110 122
45FSU 10 38 62 76 100 100
0 34 56 70 100 100
-20 30 50 62 98 100
-40 22 34 44 70 100
60FSU 10 30 50 62 86 86
0 28 44 56 86 86
-20 20 32 40 62 86
-40 12 18 24 38 60
75FSU 10 22 34 44 70 76
0 16 26 34 54 76
-20 12 18 24 38 60
-40 8 12 14 22 36
For use with Type C circuit breakers to IEC EN60898