Freezstop Regular is an industrial/commercial grade self-regulating heating cable that can be used for freeze protection or temperature maintenance of pipework and vessels in the construction and refrigeration industries. It can be cut-to-length on site to match exact piping lengths without any complicated design considerations.

Freezstop Regular is approved for use in non-hazardous, and hazardous areas to world wide standards. Its self-regulating characteristics improve safety and reliability.

Freezstop Regular will not overheat or burnout, even when overlapped upon itself. Its power output self-regulates in response to the pipe temperature.

Freezstop Regular is available with a corrosion resistant thermoplastic outer jacket (FSR-CT). When greater corrosion resistance is required a fluoropolymer outer jacket (FSR-CF) can be supplied.

Download Datasheet

Description

The installation of Freezstop Regular is quick and simple and requires no special skills or tools. Termination, splicing and power connection components are all provided in convenient kits.

Example of Applications

  • Freeze protection of pipework & vessels
  • Process temperature maintenance
  • Refrigeration Industries

Benefits

  • Can be cut to length
  • Output self-regulates in response to pipe temperature
  • No overheating or burnout
  • Inherently Temperature Safe

Download Datasheet: Freezstop Regular FSR

Maximum Continuous Exposure

Temperature (Power ON)

85°C (185°F)
Maximum Permissable Exposure

Temperature (Power OFF)

85°C (185°F)
Minimum Operating Temperature -40ºC (-40ºF)
Temperature Classification Up to 31 W/m T6 (85°C/185°F)
40 W/m or 277V T4 (135°C/275°F)
Power Supply 12 – 277 VAC
Cable Dimensions FSS-CF 12.95 x 5.95mm +/- 0.5mm
Minimum Installation Temperature -40°C (-40°F)
Minimum Bending Radius FSR-CT 35mm
FSR-CF 35mm
Weight kg/100m FSR-CT – 12.9 kg
FSR-CF – 14.8 kg
Maximum Resistance of Protective Braiding 18.2 Ohm/km
Cable Gland Thread Size M20
 
Maximum Circuit Length (m) for various circuit breaker sizes
Product
Reference
Start-Up
Termperature (°C)
230v 10A 16A 20A 32A
10FSR 10 136 198 198 198
0 122 188 188 188
-20 108 174 176 176
-40 96 154 166 166
17FSR 10 92 148 152 152
0 84 134 144 144
-20 74 118 136 136
-40 66 106 128 128
25FSR 10 74 118 124 124
0 68 108 120 120
-20 60 94 112 112
-40 52 84 106 106
31FSR 10 58 92 112 112
0 52 84 104 106
-20 46 74 92 100
-40 42 66 82 94
40FSR 10 46 74 92 98
0 42 66 84 94
-20 36 58 74 88
-40 32 52 66 84
For use with Type C circuit breakers to IEC 60898