Description
PowerHeat (AHT) can be cut-to-length at site to match exact piping lengths without any complicated design considerations.
PowerHeat (AHT) can, in most cases, replace MI cables. Series resistance MI circuits must be specifically designed for a particular pipe length and cannot be modified to suit site changes.
Example of Applications
- Freeze protection of pipes and vessels
- Temperature maintenance of processes in pipes and vessels
Benefits
- Aluminum jacket for high mechanical strength
- Available for 110V and 240VAC
- Power outputs up to 150W/m
Download Datasheet: Power Heat (AHT)
| Maximum Withstand Temperature | 500°C (932°F) |
| Maximum Energised
Temperature |
350°C (662°F)
see workpiece temperature data |
| Minimum Operating Temperature | -40°C (-40°F) |
| Power Supply | 12 – 277 VAC |
| Cable Dimensions | AHT 10.7 x 7.7mm +/- 0.5mm |
| Minimum Installation Temperature | -40°C (-40°F) |
| Minimum Bending Radius | AHT – 50mm |
| Weight kg/100m | AHT – 16.5 kg |
| Cable Gland Thread Size | AHT – M20 |
| Product
Reference |
115V | 230V | |
|---|---|---|---|
| 15 AHT | 59 | 118 | |
| 30 AHT | 42 | 83 | |
| 50 AHT | 32 | 64 | |
| 70 AHT | 26 | 54 | |
| 100 AHT | 23 | 46 | |
| 150 AHT | 19 | 37 | |
| For 10% drop variation | |||
| Heater Nominal Output (W/m) | AHT | ||
|---|---|---|---|
| 15 AHT | 350 | ||
| 30 AHT | 323 | ||
| 50 AHT | 276 | ||
| 70 AHT | 140 | ||
| 100 AHT | 140 | ||
| 150 AHT | 36 | ||
| Surface temperature limits in acordance with EN50014 | |||





Reviews